Sentinel Totus Mini |
|
Performance |
|
Airflow (nominal) |
[m³/h] |
2000 |
|
Power |
|
AC Voltage Input |
[V] |
220-240 ac (single phase) |
|
AC Frequency Input (nominal) |
[Hz] |
50/60 |
|
Supply Fuse or Cct Breaker |
[A] |
32 |
|
Rated Current |
[A] |
20 |
|
Rated Power |
[W] |
5000 |
|
Total Fan Power (max.) |
[W] |
1000 |
|
Total Frost Heater (max.) |
[W] |
4000 |
|
Power (standby) |
[W] |
0.6 |
|
DC Voltage Output |
[V] |
24 dc (18-30 V dc) at 350 mA (max.)
for switches and sensors |
|
Battery |
|
type BR1225 3 V |
|
Product Fuses |
|
Power PCB |
|
See below: Internal Fuse Values and Types |
|
Main Controller PCB |
|
See below: Internal Fuse Values and Types |
|
Environmental |
|
IP Rating - Unit |
|
IPX4 |
|
IP Rating - Comm Interface |
|
IP42 |
|
Operating Temperature |
°C |
-10 to +40 |
|
Air Intake Temperature |
°C |
-7 (minimum) to +30 (maximum) |
|
Operating Humidity |
|
0% to 95% (non-condensing)
- weatherproof unit option |
|
Storage Temperature |
°C |
-10 to +40 |
|
Storage Humidity |
|
0% to 95% (non-condensing) |
|
Condensate Pump |
|
12 m max head,
25 m max horizontal distance,
but 150 max head X distance |