AWG |
315-5.0 |
315-6.0 |
315-9.0 |
|
Efficiency/compression |
[m3/h]/[Pa] |
1000/190 |
1000/190 |
1000/190 |
|
Heater |
- phase, voltage |
[50Hz/VAC] |
~2, 400 |
~2, 400 |
~3, 400 |
|
- power consumption |
[kW] |
5,0 |
6,0 |
9,0 |
|
- min. air speed |
[m/s] |
1,5 |
1,5 |
1,5 |
|
Fan |
- phase, voltage |
[50Hz/VAC] |
~1, 230 |
~1, 230 |
~1, 230 |
|
|
- current |
[A] |
1,29 |
1,29 |
1,29 |
|
- speed |
[min-1] |
2343 |
2343 |
2343 |
|
- power consumption |
[kW] |
297 |
297 |
297 |
|
- max. airflow |
[m3/h] |
1373 |
1373 |
1373 |
|
- motor protection class |
|
IP-44 |
IP-44 |
IP-44 |
|
Terminal box protection class |
|
IP-54 |
IP-54 |
IP-54 |
|
Filter class |
|
EU3 |
EU3 |
EU3 |
|
Total sound pressure level at 1 m |
[dBA] |
68 |
68 |
68 |
|
Weight |
[kg] |
51 |
64 |
67 |
Acoustical characteristics AWG 315-9.0
Lpa dB(A) |
Lwa total dB(A) |
Lwa, dB(A) |
|
63 Hz |
125 Hz |
250 Hz |
500 Hz |
1 kHz |
2 kHz |
4 kHz |
8 kHz |
16 kHz |
|
Inlet |
|
68 |
75 |
35 |
54 |
62 |
62 |
70 |
72 |
66 |
60 |
48 |
|
Outlet |
|
65 |
72 |
32 |
59 |
61 |
65 |
64 |
66 |
63 |
59 |
49 |
|
Casing break out |
|
52 |
59 |
22 |
39 |
45 |
45 |
54 |
54 |
50 |
45 |
35 |
Measured at 1062 m3/h, 148 Pa.
The unit characteristic curves were determined in accordance with DIN 24163 resp. ISO 5801.
The sound power levels were determined in accordance with DIN 45635 resp. ISO 3744 at a distance of 1 m from the unit.
|
W |
W1 |
C |
L |
H |
Ø D |
|
550 mm |
485 mm |
285 mm |
1050 mm |
585 mm |
250 mm |
AWG 250-1.2
AWG 250-5.0, AWG 250-6.0
AWG 250-9.0
C - Circular fan
D - Electrical heater
|
|
 |
|
 |
|
|