VEKU 700 VE
 |
(1) supply
(2) exhaust |
|
VEKU |
700VE |
|
Efficiency/compression |
[m3/h]/[Pa] |
500/160 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
|
- power consumption |
[kW] |
3,0 |
|
Pre-heater for heat exchanger |
[kW] |
1,2 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
- supply |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
60% |
|
Maks. power consumption |
[kW/A] |
4,71/20,5 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU3 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
30 |
|
Weight |
[kg] |
82,0 |
VEKU 700 VW
 |
(1) supply
(2) exhaust |
|
VEKU |
700VW |
|
Efficiency/compression |
[m3/h]/[Pa] |
500/200 |
|
Water heater |
- power |
[kW] |
NVS 200 |
|
|
- water Tin/Tout |
[°C] |
|
|
- water pressure drop |
[kPa] |
|
Pre-heater for heat exchanger |
[kW] |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
- supply |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
60% |
|
Maks. power consumption |
[kW/A] |
4,71/20,5 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU3 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
30 |
|
Weight |
[kg] |
82,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VEKU 700VE was measured at 700m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VEKU 700VW was measured at 700m3/h, at temperature range from -20°C to +20°C.
VEKU 700 HE
 |
(1) supply
(2) exhaust |
|
VEKU |
700HE |
|
Efficiency/compression |
[m3/h]/[Pa] |
500/200 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
|
- power consumption |
[kW] |
3,0 |
|
Pre-heater for heat exchanger |
[kW] |
1,2 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
- supply |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
60% |
|
Maks. power consumption |
[kW/A] |
4,71/20,5 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU3 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
57,0 |
VEKU 700 HW
 |
(1) supply
(2) exhaust |
|
VEKU |
700HW |
|
Efficiency/compression |
[m3/h]/[Pa] |
500/180 |
|
Water heater |
- power |
[kW] |
4,7 |
|
|
- water Tin/Tout |
[°C] |
80/60 |
|
|
- water flow rate |
[l/s] |
0,06 |
|
|
- water pressure drop |
[kPa] |
4,9 |
|
|
- kvs value |
[m3/h] |
1,0 |
|
Pre-heater for heat exchanger |
[kW] |
1,2 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
- supply |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
Motor protection class |
|
IP-54 |
|
Thermal efficiency |
|
60% |
|
Maks. power consumption |
[kW/A] |
1,71/7,5 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU3 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
50 |
|
Weight |
[kg] |
57,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VEKU 700HE was measured at 700m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VEKU 700HW was measured at 700m3/h, at temperature range from -20°C to +20°C.
VEKU 700 PE
 |
(1) supply
(2) exhaust |
|
VEKU |
700PE |
|
Efficiency/compression |
[m3/h]/[Pa] |
500/160 |
|
Heater |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
|
- power consumption |
[kW] |
3,0 |
|
Pre-heater for heat exchanger |
[kW] |
1,2 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
- supply |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
Motor protection class |
|
IP-44 |
|
Thermal efficiency |
|
57% |
|
Maks. power consumption |
[kW/A] |
4,71/20,5 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
30 |
|
Weight |
[kg] |
57,0 |
VEKU 700 PW
 |
(1) supply
(2) exhaust |
|
VEKU |
700PW |
|
Efficiency/compression |
[m3/h]/[Pa] |
500/160 |
|
Water heater |
- power |
[kW] |
NVS 160 |
|
|
- water Tin/Tout |
[°C] |
|
|
- water pressure drop |
[kPa] |
|
Pre-heater for heat exchanger |
[kW] |
1,2 |
|
Fans |
- phase/voltage |
[50Hz/VAC] |
~1, 230 |
|
- exhaust |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
- supply |
- power/current |
[kW/A] |
0,255/1,12 |
|
|
- fan speed |
[min-1] |
2000 |
|
Motor protection class |
|
IP-44 |
|
Thermal efficiency |
|
57% |
|
Maks. power consumption |
[kW/A] |
4,71/20,5 |
|
Automatic control |
|
integrated |
|
Filter class - exhaust |
|
EU5 |
|
Filter class - supply |
|
EU5 |
|
Thermal insulation |
[mm] |
30 |
|
Weight |
[kg] |
57,0 |
Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VEKU 700PE was measured at 700m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VEKU 700PW was measured at 700m3/h, at temperature range from -20°C to +20°C.
VEKU 700VE, VEKU 700VW
 |
|
L |
W |
H |
Ø D |
H1 |
F |
|
950 mm |
950 mm |
895 mm |
200 mm |
- |
30 mm |
|
VEKU 700HE, VEKU 700HW
 |
|
L |
W |
H |
Ø D |
H1 |
F |
|
VEKU 700HE |
|
1170 mm |
504 mm |
690 mm |
250 mm |
30 mm |
40 mm |
|
VEKU 700HW |
|
1320 mm |
504 mm |
690 mm |
250 mm |
30 mm |
40 mm |
|
VEKU 700PE, VEKU 700PW
 |
|
L |
W |
W1 |
W2 |
H |
H1 |
H2 |
H3 |
Ø D |
|
1200 mm |
300 mm |
134 mm |
134 mm |
775 mm |
190 mm |
190 mm |
100 mm |
250 mm |
|
VEKU 700VE
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KE - electrical heater
PE - anti-freeze heater for heat exchanger
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU3)
TJ - temperature sensor for supply air
TL - temperature sensor for fresh air
TE - temperature sensor for extract air
DTJ - humidity + temperature sensor
|
VEKU 700VW
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
NVS - optionally supplied water heater
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
PE - anti-freeze heater for heat exchanger
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU3)
TJ - temperature sensor for supply air
TL - temperature sensor for fresh air
TE - temperature sensor for extract air
DTJ - humidity + temperature sensor
M1 - optionally supplied mixing valve and motor |
VEKU 700HE
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KE - electrical heater
PE - anti-freeze heater for heat exchanger
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU3)
TJ - temperature sensor for supply air
TL - temperature sensor for fresh air
TE - temperature sensor for extract air
DTJ - humidity + temperature sensor |
VEKU 700HW
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KV - water heater
PE - anti-freeze heater for heat exchanger
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU5)
TL - temperature sensor for fresh air
TE - temperature sensor for extract air
T1 - antifrost thermostat
TV - antifrost sensor
TJ - temperature sensor for supply air
M1 - optionally supplied mixing valve and motor |
VEKU 700PE
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
KE - electrical heater
PE - anti-freeze heater for heat exchanger
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU5)
TJ - temperature sensor for supply air
TL - temperature sensor for fresh air
TE - temperature sensor for extract air
DTJ - humidity + temperature sensor |
VEKU 700PW
A - fresh air
B - supply air
C - extract air
D - exhaust air |
|
NVS - optionally supplied water heater
IV - exhaust air fan
PV - supply air fan
PR - plate heat exchanger
PE - anti-freeze heater for heat exchanger
PF - filter for supply air (class EU5)
IF - filter for extract air (class EU5)
TJ - temperature sensor for supply air
TL - temperature sensor for fresh air
TE - temperature sensor for extract air
DTJ - humidity + temperature sensor
M1 - optionally supplied mixing valve and motor |
|
|
 |
|
 |
|
|