VEKU 3000



VEKU 3000 HE
(1) supply
(2) exhaust

VEKU 3000HE
Efficiency/compression [m3/h]/[Pa] 3000/360
Heater - phase/voltage [50Hz/VAC] ~3, 400
- power consumption [kW] 24,0 (9+15)
Pre-heater for heat exchanger [kW] -
Fans - phase/voltage [50Hz/VAC] ~3, 400
  - exhaust - power/current [kW/A] 2,5/4,1
- fan speed [min-1] 1300
  - supply - power/current [kW/A] 2,5/4,1
- fan speed [min-1] 1300
Motor protection class IP-54
Thermal efficiency 59%
Maks. power consumption [kW/A] 29,0/44,7
Automatic control opcja
Filter class - exhaust EU5
Filter class - supply EU5
Thermal insulation [mm] 50
Weight [kg] 395,0


VEKU 3000 HW
(1) supply
(2) exhaust

VEKU 3000HW
Efficiency/compression [m3/h]/[Pa] 3000/260
Water heater - power [kW] 20,2
- water Tin/Tout [°C] 80/60
- water flow rate [l/s] 0,25
- water pressure drop [kPa] 10,3
- kvs value [m3/h] 2,8
Pre-heater for heat exchanger [kW] -
Fans - phase/voltage [50Hz/VAC] ~3, 400
  - exhaust - power/current [kW/A] 2,5/4,1
- fan speed [min-1] 1300
  - supply - power/current [kW/A] 2,5/4,1
- fan speed [min-1] 1300
Motor protection class IP-54
Thermal efficiency 59%
Maks. power consumption [kW/A] 5,0/8,2
Automatic control opcja
Filter class - exhaust EU5
Filter class - supply EU5
Thermal insulation [mm] 50
Weight [kg] 395,0


Air flow temperature range from -20°C to +40°C
Designed for operation indoors only.
Thermal efficiency of VEKU 3000HE was measured at 1900m3/h, at temperature range from -20°C to +20°C.
Thermal efficiency of VEKU 3000HW was measured at 1900m3/h, at temperature range from -20°C to +20°C.