Single plain cut-off damper for fire ventilation systems:
The cut-off fire dampers enable retaining the fire resistance of the whole ventilation partition. In the event of fire, these dampers enable the partition, through which ventilation and air-conditioning ducts run, to retain its fire resistance properties. In normal operating conditions damper’s screen is open. If a fire breaks out, the damper is closed.
Available from the Stock:
W ciągłej sprzedaży z magazynu, Centrum Klima S.A. oferuje poniższe typy klap ppoż.:
- MCR-FID S/O EIS-60 RST in the range d=100-500 mm,
- MCR-FID S-p/O EIS-120 RST in the range d=100-500 mm.
mcr FID S - jednopłaszczyznowa klapa odcinająca oraz do systemów wentylacji pożarowej:
Fire protection class:
- EIS90, EIS90AA, ES120, EIS120AA - depends on the model and assembly location
Versions:
- cut-off dampers - S
- for fire ventilation systems (smoke-exhausting) - V
- for double-function ducts (combined systems) - M
Designed for:
- Dampers of the mcr FID S/V /P, mcr FID S/V p/P, mcr FID S/V /O, mcr FID S/V p/O types can be manufactured without a thermal release unit. They are used in fire ventilation systems. In normal operating conditions, the damper’s screen is closed. In the event of fire the screen opens, therefore smoke and fire gases can be exhausted through the device.
- Dampers of the FID S/M /P, mcr FID S/M p/P, mcr FID S/M /O, mcr FID S/M p/O types are also designed to be used in systems in which ventilation ducts perform two functions: the functions of a general ventilation system as well as a smoke exhaust system; where these ducts run through building partitions. In normal operating conditions, the damper’s screen is open. In the event of fire, it remains open or closes. These dampers are not fitted with thermal release units.
Types of dampers:
- mcr FID S/S /P; mcr FID S/V /P; mcr FID S/M /P - rectangular dampers without an insulating separator
- mcr FID S/S /O; mcr FID S/V /O; mcr FID S/M /O - round dampers without an insulating separator
- mcr FID S/S p/P; mcr FID S/V p/P; mcr FID S/M p/P - rectangular dampers with an insulating separator
- mcr FID S/S p/O; mcr FID S/V p/O; mcr FID S/M p/O - round dampers with an insulating separator
Dimensions:
- cut-off dampers of the mcr FID S/... /P and mcr FID S/... /O types are manufactured in the following dimensions: width - from 200 to 1200mm, height – from 200 to 1200mm; diameter from 125mm to 1000mm. Apart from standard dimensions, dampers can be customised to any size within the specified ranges. Maximum cross-section area of the mcr FID S/P damper is 1 m²
- cut-off dampers of the mcr FID S/... /P and mcr FID S/... /O types are manufactured in the following dimensions: width - from 200 to 1500mm, height – from 200 to 1500mm; diameter from 125mm to 1000mm. Apart from standard dimensions, dampers can be customised to any size within the specified ranges. Maximum cross-section area of the mcrFID S/... p/P damper is 1.8 m²
ITB Technical Approval AT-15-6990/2007
Certificate of Conformity ITB CZ-ITB-1491/W
mcr FID PRO - single-plane damper for fire ventilation systems:
Fire protection class:
Versions:
- cut-off dampers - S
- for fire ventilation systems (smoke-exhausting) - V
- for double-function ducts (combined systems) - M
Purpose:
- Cut-off fire dampers of the mcr FID PRO type with the thermal release unit are designed to be used in general ventilation systems where these systems run through building partitions (mcr FID PRO/S designation). In the event of fire, these dampers enable the partition, through which ventilation and air-conditioning ducts run, to retain its fire resistance properties. In normal operating conditions the damper’s screen is open. If fire breaks out, the damper’s screen closes.
- Dampers of the mcr FID PRO types can be manufactured without the thermal release unit. They are used in fire ventilation systems (mcr FID PRO/V designation). In normal operating conditions, the damper’s screen is closed. In the event of fire the screen opens, therefore smoke and fire gases can flow through the device.
- Fire cut-off dampers of the mcr FID PRO type are also designed to be used in systems in which ventilation ducts perform two functions: the functions of a general ventilation system as well as a smoke exhaust system; at points where these systems run through building partitions (mcr FID PRO designation). In normal operating conditions the damper’s screen is open. In the event of fire, it remains open or closes, depending on the fire-tackling manner. These dampers are not fitted with thermal releases.
Types of dampers:
- mcr FID PRO /S; mcr FID PRO /V; mcr FID PRO /M - round dampers in the form of a sleeve
- mcr FID PRO /S; mcr FID PRO /V; mcr FID PRO /M - round dampers in the form of a nipple
- mcr FID PRO /S; mcr FID PRO /V; mcr FID PRO /M - round dampers in the form of a flange
ITB Technical Approval AT-15-6990/2007
Certificate of Conformity ITB CZ-ITB-1491/W
|
|
 |
|
 |
|
|